风管阀件的安装
Installation of air duct valve
1.风阀的安装
1. Installation of air valve
(1)安装蝶阀、多叶调节阀、防火防烟调节阀等各类风阀前,应检查其结构是否牢固,调节、制动、定位等装置应准确灵活。
(1) Before installing butterfly valve, multi blade control valve, fire
and smoke control control valve and other air valves, check whether
their structures are firm, and the adjustment, braking, positioning and
other devices should be accurate and flexible.
(2)安装时注意风阀的气流方向,应按风阀外壳标注的方向安装,不得装反。
(2) During installation, pay attention to the air flow direction of the
air valve. The air valve shall be installed in the direction marked on
the air valve housing, and shall not be installed reversely.
(3)风阀的开闭方向、开启程度应在阀体上有明显和准确的标志。
(3) The opening and closing direction and opening degree of the air
valve shall be clearly and accurately marked on the valve body.
(4)止回阀宜安装在风机压出端,开启方向必须与气流方向一致。
(4) The check valve should be installed at the outlet end of the fan,
and the opening direction must be consistent with the air flow
direction.
(5)阀门在建筑吊顶_上或在风道中安装时,应在吊顶板上或风管壁上设检修孔,一般孔尺寸不小于450X450mm。
(5) Valve in building ceiling_ When installing on or in the air duct,
the manhole shall be set on the ceiling plate or the air duct wall, and
the size of the manhole shall not be less than 450X450mm generally.
(6)变风量末端装置安装,应设独立支吊架,与风管连接前应做动作试验。
(6) For the installation of VAV terminal devices, independent supports
and hangers shall be provided, and action tests shall be conducted
before connection with air ducts.
(7)各类排气罩安装宜在设备就位后进行。风帽滴水盘(槽)安装要牢固、不得渗漏。凝结水应引流到指定位置。
(7) Various exhaust hoods should be installed after the equipment is in
place. The drip pan (groove) of the hood shall be firmly installed
without leakage. Condensate shall be drained to the designated position.
(8)斜插板风阀的安装,阀板必须为向上拉启;水平安装时,阀板应为顺气流方向插入。
(8) When installing the inclined gate air valve, the valve plate must be
pulled upward; When installed horizontally, the valve plate shall be
inserted along the airflow direction.
州苗木 保定电动门 保定空压机 化粪池模具 微型蠕动泵 保定强夯 收费岛模具设计要求,防止装错。防火阀易熔件应在系统试运转之前安装,且应迎气流方向。防火分区隔墙两侧的防火阀,距墙表面不应大于200mm。
a. There are horizontal, vertical, left and right fire dampers. The
installation shall be in accordance with the design requirements to
prevent incorrect installation. The fusible parts of fire damper shall
be installed before the system commissioning, and shall face the airflow
direction. The fire dampers on both sides of the partition wall of the
fire compartment shall not be more than 200mm from the wall surface.
b.安装前应先检查阀i门]外形操作机构是否完好,检查动作的灵活性,然后再进行安装。
b. Before installation, check whether the operating mechanism of valve i
door] shape is in good condition, and check the flexibility of action
before installation.